Schneider ATV320 Fault List: Codes, Causes & Troubleshooting Guide

October 8, 2026 · Automation
Schneider ATV320 Fault List: Codes, Causes & Troubleshooting Guide
SCHNEIDER ATV320 • VFD TROUBLESHOOTING
Schneider ATV320 Fault Codes, Causes & Practical Troubleshooting

The Schneider ATV320 fault list helps technicians identify what the drive has detected. The code is only the starting point—the real cause may be the motor, electrical supply, wiring, mechanical load, communication network, cooling system, or drive configuration.

Before resetting an ATV320 or replacing the drive, note the displayed fault code and when the trip occurs. A fault during acceleration can point in a different direction from the same machine failing after several hours of operation.

This guide gives electrical engineers, maintenance teams, industrial companies, contractors, and machine operators a practical starting point for common ATV320 faults.

Schneider ATV320 Fault List – Quick Reference

Start with the displayed code, then inspect the related part of the system. Do not assume the VFD itself has failed.

Fault Code Meaning Possible Cause Check First
OCF Overcurrent Heavy load, motor issue, incorrect drive settings Motor, mechanical load and motor parameters
OLF Motor overload Excessive motor current or mechanical load Motor load and nameplate settings
OHF Drive overtemperature Restricted airflow, high temperature or cooling issue Cooling fan, filters and panel ventilation
USF Undervoltage Low supply voltage or temporary voltage dip Incoming electrical supply
OSF Mains overvoltage Excessive supply voltage or power-quality issue Incoming supply voltage
PHF Input phase loss Missing phase or unstable incoming supply Phases, breakers, fuses and terminals
OPF1 One output phase loss Motor cable or terminal connection problem Drive-to-motor wiring
OPF2 Output phases lost Motor disconnected or output circuit problem Motor wiring and output circuit
SCF1 Motor short circuit Motor or output cable short circuit Motor cable, terminals and insulation
SOF Overspeed Load condition or incorrect speed-related settings Motor, mechanical load and parameters

ATV320 Overcurrent Fault – OCF

An OCF fault means the ATV320 has detected excessive motor current. Check whether the motor information entered into the drive matches the actual motor nameplate and inspect the driven machine for excessive mechanical load.

Real example: A loaded conveyor trips every time it starts. The drive may be healthy—the real cause could be a tight bearing, overloaded conveyor, incorrect motor data, or acceleration that is too aggressive for the application.

For recurring drive faults, see EMAN FTC's VFD Installation & Commissioning Services .

ATV320 Motor Overload Fault – OLF

An OLF fault points to a motor overload condition. Check the actual machine load together with rated motor current, voltage, frequency, and other motor data stored in the drive.

Real example: A pump operates normally at low demand but trips when process demand increases. Before changing protection values, check whether the pump is mechanically overloaded and whether the motor parameters match the installed motor.

ATV320 Overtemperature Fault – OHF

An OHF fault indicates that the drive temperature is too high. Check cooling fans, filters, enclosure ventilation, ambient temperature, and motor loading.

Real example: A VFD runs normally in the morning but starts tripping later in the day. Before replacing it, check whether panel temperature increases during peak conditions or whether dust is restricting airflow.

If the ATV320 is installed inside a larger industrial panel, see our Control Panel Troubleshooting & Maintenance Services .

ATV320 Undervoltage and Overvoltage Faults

A USF fault points toward low incoming supply voltage or a temporary voltage dip. Measure the incoming supply and check whether the problem occurs during starting or heavy loading.

An OSF fault indicates an overvoltage condition. Check the supply and operating conditions before changing drive parameters.

Real example: If several drives in the same facility report voltage-related faults at almost the same time, investigate the incoming electrical supply before treating each VFD as a separate failure.

ATV320 Input Phase Loss – PHF

A PHF fault directs attention to the incoming supply. Check whether all phases are present and inspect upstream breakers, fuses, terminals, and cable connections.

A loose connection can produce an intermittent phase problem, so a normal reading while the equipment is stopped does not always prove that the supply remains stable under load.

ATV320 Output Phase and Short-Circuit Faults

OPF1 indicates loss of one motor output phase. Start with the cable and terminal connections between the ATV320 and the motor.

OPF2 may appear when the motor is disconnected, an output contactor is open, or there is a problem in the motor output circuit.

For SCF-related faults, inspect the motor and output wiring for phase-to-phase or phase-to-ground problems. The motor terminals and insulation condition may also need testing.

For electrical measurements and insulation checks, explore EMAN FTC's Electrical Testing Equipment .

ATV320 Overspeed Fault – SOF

An SOF fault means the ATV320 has detected an overspeed condition. The cause may involve the mechanical load, motor setup, speed-control conditions, or a high-inertia application.

Real example: A high-inertia machine continues driving the motor while the ATV320 is trying to slow it down. Resetting the drive may clear the code temporarily, but it does not remove the condition responsible for the trip.

Check When the ATV320 Fault Occurs

The timing of the trip can provide an important clue during troubleshooting.

When the Fault Appears Areas to Investigate
Immediately after power-up Supply, configuration, communication or internal drive condition
When START is commanded Motor wiring, control signals, interlocks and motor parameters
During acceleration Mechanical load, motor data, acceleration settings and current
During normal operation Load, supply, motor condition, temperature and wiring
During deceleration Load inertia, regenerative conditions and deceleration settings
After long operation Cooling, panel temperature, ventilation and motor loading

Do Not Troubleshoot the ATV320 in Isolation

Not every VFD problem starts inside the drive. A motor may refuse to start because of an active PLC interlock even when the ATV320 itself is healthy.

Communication problems can originate from the PLC, HMI, network cable, Modbus settings, communication modules, or control wiring. Repeated trips may also involve breakers, contactors, terminals, sensors, the motor, or supply voltage.

For faults involving several parts of the control system, see EMAN FTC's Control System Fault Analysis Services .

For command and interlock problems, see our PLC Troubleshooting & Maintenance Services .

For display or communication issues, see HMI Troubleshooting & Configuration Services and SCADA System Integration & Support .

When Should You Call a VFD Technician?

If the same ATV320 fault returns after the obvious external causes have been checked, avoid repeatedly resetting the drive.

Recurring overcurrent, short-circuit, overheating, voltage, communication, or internal faults should be investigated with the motor, wiring, control panel, and automation system considered together.

EMAN FTC provides VFD troubleshooting, parameter configuration, installation, integration, maintenance, and commissioning support for industrial applications in Saudi Arabia.

Frequently Asked Questions

What does OCF mean on a Schneider ATV320?

OCF indicates an overcurrent condition. Check the mechanical load, motor condition, motor data, wiring, and the operating condition when the trip occurs before replacing the drive.

Why does my ATV320 keep showing OLF?

OLF is associated with motor overload. Check the actual machine load and make sure the motor nameplate information entered into the drive matches the installed motor.

Can a motor or cable cause an ATV320 fault?

Yes. Motor insulation problems, loose terminals, damaged output cables, missing phases, or mechanical loading can create faults that appear on the VFD.

Should I reset the ATV320 every time it trips?

Not automatically. If the same fault keeps returning, identify the cause first. Repeated resetting can hide an electrical, mechanical, cooling, or configuration problem.

Can a PLC interlock stop an ATV320 from running?

Yes. A healthy VFD may remain stopped if the PLC, safety circuit, sensor, or process interlock is not allowing the run command.

Important: ATV320 fault handling can depend on the drive model, configuration, firmware, motor data, and installed options. Confirm critical troubleshooting and parameter changes against the Schneider Electric documentation for your exact ATV320 drive.

Need Help With a Schneider ATV320 Fault?

Send the fault code, ATV320 model, motor nameplate details, control-panel photos, site location, and a short explanation of when the problem occurs.

This information helps narrow the possible cause before troubleshooting begins.

Phone / WhatsApp: +966 58 339 5756
Email: info@emanftc.com
Website: emanftc.com